SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
87
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
More than 10
seconds passed
since power-on
Shut off power.
Remove the compressor lead wire.
No defective
insulation on
compressor
No defective
insulation on entire
product
High pressure
switch is properly
connected.
Leakage detector
PCB fuse is not
blown.
Recover all wiring.
Turn on the power.
Leakage detector
PCB is energized.
High pressure
switch is energized
at both ends.
YES
NO
YES
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Reset the power with the
operation switch set to OFF.
Earth leakage (breaker ON/
OFF): E2
Replace the defective parts.
Earth leakage (leakage
detector PCB): E2
Replace the defective parts.
Earth leakage (leakage
detector PCB): E2
Correct connection.
Replace the leakage
detector PCB.
Replace the leakage
detector PCB.
Replace the high pressure
switch.
It is likely that earth leakage
occurred due to temporary
liquid return or refrigerant
slugging.
Earth leakage is possible in
the event of power failure
during operation or
prolonged power shutoff.