SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
91
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the stop
valve open?
(1)Mount a pressure gauge on the low pressure
service port.
(2)Reset the operation and then restart the
operation.
Are the
characteristics of
the low pressure
sensor normal?
(See
∗
1.)
Service Checker
Connect the service checker to compare the “low pressure”
value and the actual measurement value by pressure
sensor (Refer to
∗
1) by using the service checker.
Check if the “low
pressure” value and the
actual measurement
value by pressure sensor
are the same.
· The low pressure sensor is normal, and the pressure
detected with the PCB is also normal.
· The low pressure has really become low.
Referring to information on P135, remove the causes
by which the low pressure has become low.
CHECK 6
∗
1:Make a comparison between the voltage of the pressure sensor and that read by the
pressure gauge.
∗
2:Make measurement of voltage of the pressure sensor.
NO
YES
NO
YES
NO
YES
Open the stop valve.
Replace the low pressure sensor.
Replace the main PCB (A1P).
+5V
Connector for low pressure sensor
(Blue)
(4)
(3)
(2)
(1)
Red
Black
White
Micro-controller
A/D input
Make measurement of DC voltage between these wires.
Low
pressure
sensor
Checking for clog
To check for the presence of clog, measure the pipe temperatures at the locations before and after
the check point.
(1) Electronic expansion valve (2) Secondary equipment filter (3) Dryer (4) Outdoor unit filter