![Daikin LRLEQ10AY1(E) Service Manual Download Page 79](http://html1.mh-extra.com/html/daikin/lrleq10ay1-e/lrleq10ay1-e_service-manual_502370079.webp)
Troubleshooting
SiENBE28-901
78
Air Cooled Refrigeration Condensing Unit
2) In Setting Modes 1-14 and on, it is possible to use the LED to check the error and retry
details, using the same steps as previously described (see the next page).
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
NO
Setting
Large item
Middle item
Small item
Description
1
Setting Mode 1, No. 1
Malfunction
output
System
Reversed phase
H7P blinks when reversed phase is detected.
2
Setting Mode 1, No. 1
INV earth leakage
H6P blinks when INV earth leakage is detected.
3
Setting Mode 1, No. 1
STD1 earth leakage H5P blinks when STD1 earth leakage is detected.
4
Setting Mode 1, No. 1
STD2 earth leakage H4P blinks when STD2 earth leakage is detected.
5
Setting Mode 1, No. 2
EV
EV1
H7P blinks when EV1 error occurs.
6
Setting Mode 1, No. 2
EV2
H6P blinks when EV2 error occurs.
7
Setting Mode 1, No. 2
EV3
H5P blinks when EV3 error occurs.
8
Setting Mode 1, No. 3
Pressure sensor
HP
H5P blinks when HP sensor error occurs.
9
Setting Mode 1, No. 3
LP1
H7P blinks when LP1 sensor error occurs.
10
Setting Mode 1, No. 4
Temperature sensor 1
Td1
H7P blinks when Td1 sensor error occurs.
11
Setting Mode 1, No. 4
Td2
H6P blinks when Td2 sensor error occurs.
12
Setting Mode 1, No. 4
Td3
H5P blinks when Td3 sensor error occurs.
13
Setting Mode 1, No. 4
Ti1
H4P blinks when Ti1 sensor error occurs.
14
Setting Mode 1, No. 5
Temperature sensor 2
Ta
H7P blinks when Ta sensor error occurs.
15
Setting Mode 1, No. 5
Tg
H6P blinks when Tg sensor error occurs.
16
Setting Mode 1, No. 5
TL
H5P blinks when TL sensor error occurs.
17
Setting Mode 1, No. 6
Current sensor
CT1
H7P blinks when CT1 sensor error occurs.
18
Setting Mode 1, No. 6
CT2
H6P blinks when CT2 sensor error occurs.
19
Setting Mode 1, No. 7
Protection device
HPS
H7P blinks when HPS is detected.
20
Setting Mode 1, No. 7
HPSL
H6P blinks when HPSL is detected.
21
Setting Mode 1, No. 8
Transmission
INV
H7P blinks when INV transmission error occurs.
22
Setting Mode 1, No. 9
INV error 1
L1
H7P blinks when L1 error occurs.
23
Setting Mode 1, No. 9
L4
H6P blinks when L4 error occurs.
24
Setting Mode 1, No. 9
L5
H5P blinks when L5 error occurs.
25
Setting Mode 1, No. 9
L8
H4P blinks when L8 error occurs.
26
Setting Mode 1, No. 9
L9
H3P blinks when L9 error occurs.
27
Setting Mode 1, No. 10
INV error 2
E5
H7P blinks when E5 error occurs.
28
Setting Mode 1, No. 10
U2
H6P blinks when U2 error occurs.
29
Setting Mode 1, No. 10
P1
H5P blinks when P1 error occurs.
30
Setting Mode 1, No. 10
P2
H4P blinks when P2 error occurs.
31
Setting Mode 1, No. 11
Malfunction of fan
E7 (FAN1)
H7P blinks when E7 error occurs.
32
Setting Mode 1, No. 11
H7 (FAN1)
H6P blinks when H7 error occurs.
33
Setting Mode 1, No. 11
E7 (FAN2)
H7P blinks when E7 error occurs.
34
Setting Mode 1, No. 11
H7 (FAN2)
H6P blinks when H7 error occurs.
35
Setting Mode 1, No. 14
Malfunction
output
Malfunction contents
(latest)
—
0~63 (6bit)
(See the list of malfunction codes.)
36
Setting Mode 1, No. 15
Malfunction contents
(one before)
—
0~63 (6bit)
(See the list of malfunction codes.)
37
Setting Mode 1, No. 16
Malfunction contents
(two before)
—
0~63 (6bit)
(See the list of malfunction codes.)
38
Setting Mode 1, No. 17
Software number
display
—
0~63 (6bit)
39
Setting Mode 1, No. 18
HP
—
0~63 (6bit)
40
Setting Mode 1, No. 19
Software version
display
—
0~63 (6bit)
41
Setting Mode 1, No. 20
Retry description
(latest)
—
0~63 (6bit)
(See the list of malfunction codes.)
42
Setting Mode 1, No. 21
Retry description (one
before)
—
0~63 (6bit)
(See the list of malfunction codes.)
43
Setting Mode 1, No. 22
Retry description (two
before)
—
0~63 (6bit)