SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
75
2-2. Procedures to be taken after beginning emergency operation until compressor
replacement is complete and normal operation resumes
1.Change the outdoor unit operation switch from "LOCAL" or "REMOTE" to "OFF".
2.Turn off the outdoor unit's main breaker.
3.Replace the defective compressor with a new one.
4.Turn the outdoor unit breaker back on.
(*Make sure that the operation switch is set to "OFF" before turning on the main
breaker.)
5.Change the outdoor unit operation switch from "OFF" to "LOCAL" or "REMOTE".
3. Contact our service department for details about the setting procedures for the
AIRNET and service checker, and the precautions for use.
3-1. When using the AIRNET:
Specify the outdoor unit AirNet address settings (Setting Mode 2-06).
Specify the virtual indoor unit address settings (Setting Mode 2-16).
(The settings described above are necessary even if you are not using the AIRNET,
but are using an ST controller.)
(Contact our service department when connecting a system to a VRV or other
systems.)
3-2. When using a service checker:
Specify the virtual indoor address settings (Setting Mode 2-16).
Note:
Be sure to stop the system operation (compressors) before running a test of the AIRNET or
using a service checker.