SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
111
Troubleshooting
∗
1: Voltage measurement point
∗
2: Refer to “Voltage Characteristics of Pressure Sensor” table on P.139.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
1.Set the high pressure gauge.
2.Connect a RAM monitor.
Are the characteristics of
the high pressure sensor
normal? (Make a
comparison between the
voltage characteristics
(
∗
1) and the gauge
pressure.)
YES
NO
If the PCB pressure
detection normal? (Make
a comparison between
the checker pressure
data and the voltage
characteristics (
∗
1).)
YES
NO
Reset the operation, and then
restart the outdoor unit.
Are the characteristics of
the high pressure sensor
normal? (*2)
YES
NO
Replace the high pressure sensor.
Replace the main PCB.
Replace the high pressure sensor.
Replace the main PCB.
Outdoor unit PCB (A2P)
+5V
GND
Micro-computer
A/D input
∗
2 Measure DC voltage here.
Connector
(Red)
X32A
(4)
(3)
(2)
(1)
Red
Black
White
H
igh pr
essur
e se
nsor
(S1NPH)
(V2807)