SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
123
Troubleshooting
*1. Connect and disconnect the connector to make sure it is securely connected.
*2. List of types of inverter PCB
Applicable model
Type
LRMEQ5~20AY1
LRLEQ5~20AY1
PC0509-2(A)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the connector
connecting between
each control PCB and
each inverter PCB
securely connected?
(See *1)
YES
NO
Is the type of the
inverter PCB correct?
(See *2)
YES
NO
The insulation
resistance of the INV
compressor is not more
than 100k
Ω
.
NO
YES
The insulation
resistance of the fan
motor is not more
than 1M
Ω
.
NO
YES
The micro controller
normal monitor LED
(green) on the main PCB
(A3P) is blinking.
YES
NO
The micro controller
normal monitor LED
(green) on the inverter
PCB is blinking.
YES
NO
The "
LC
"
malfunction recurs.
NO
YES
Properly connect the connector.
Replace with a proper PCB.
Replace the INV compressor.
Replace the fan motor.
Not the "
LC
" malfunction. Recheck
for the malfunction code.
Replace the inverter PCB.
Replace the outdoor unit main PCB
(A1P).
Continue the operation.
Factors such as instantaneous
power failure are supposed.