Field Settings
SiENBE28-901
34
Air Cooled Refrigeration Condensing Unit
(2) Setting in service mode
Using pushbuttons on the Main PCB (A1P) enables a variety of settings shown below.
The following 4 modes are available.
Procedure for changing mode
Steps to change mode
Caution
Turn off the RUN switch of the outdoor unit in case of the setting.
a. Setting mode 1 ......
(H1P: OFF)
Initial state (while in normal operation): Used to make setting of the method of "Cool/Heat
selection".
This mode is displayed while in "malfunction",
"low noise control", and "demand control" as well.
b. Setting mode 2
Setting mode 3 ......
(H1P: ON)
Used to make changes of operating conditions or settings of a variety of addresses,
mainly for service work.
c. Monitor mode ......
(H1P: BLINK)
Used to check the contents set in Setting mode 2.
While in each mode, use the MODE button to change settings as shown below.
BS1
MODE
BS2
SET
BS3
RETURN
BS4
BS5
RESET
Setting mode 2
MODE
H1P
ON
Setting mode 1
MODE
H1P
OFF
Monitor mode
MODE
H1P
BLINK
Setting mode 3
Simultaneously press and hold the
BS1 (MODE) and BS3 (RETURN)
for a period of 5 seconds.
Press and hold the BS1
(MODE) for a period of
five seconds.
Press the BS1 (MODE)
once.
(Normal)
Press the BS1
(MODE) once.
OP : Select mode with the use of BS2
(SET) in each selection step.
Press and hold the BS1
(MODE) for a period of
five seconds.
Setting mode 1
(Initial state)
Setting mode 2
Press the BS1 (MODE) once.
Selection of
setting items
SET
Selection of
setting contents
SET
Press the BS3
(RETURN).
Press the BS3
(RETURN).
Display of
setting contents
Press the BS3
(RETURN).
Press the BS1
(MODE).
Monitor mode
Selection of
check items
SET
Display of contents
Press the BS3
(RETURN).
Press the BS3
(RETURN).
Press the BS1
(MODE).