SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
103
6.6.10 “
H3
” Malfunction Related to High Pressure Switch
Remote
Controller
Display
H3
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Detect continuity in the high pressure switch in the protective device circuit.
Malfunction
Decision
Conditions
While the compressor stops running, there is no continuity in the high pressure switch.
Supposed
Causes
Faulty high pressure switch
Broken wire in the harness of high pressure switch
Faulty connection of the connector of high pressure switch
Faulty outdoor unit PCB
Broken wire in lead wire
Troubleshooting
*1 The table below shows the connector numbers of the high pressure switch.
Model
Relevant PCB
Electric symbol
Connector No.
LRMEQ5, 6AY1
LRLEQ5, 6AY1
A1P
S1PH
X2A
LRMEQ8, 10, 12AY1
LRLEQ8, 10, 12AY1
A1P
S1PH
S2PH
X2A
X3A
LRMEQ15, 20AY1
LRLEQ15, 20AY1
A1P
S1PH
S2PH
S3PH
X2A
X3A
X4A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the high pressure
switch connector
properly connected to
the outdoor unit PCB?
(See*1)
YES
NO
Stop the compressor for a
period of 10 minutes, and then
carry out the following checks.
Is there continuity in
the high pressure
switch?
YES
NO
Is there continuity in
the lead wire?
YES
NO
Properly connect it.
Replace the high pressure switch
having no continuity in it.
* Normal resistance:
Not more than 10
Ω
Replace the lead wire.
Replace the outdoor PCB.