Troubleshooting
SiENBE28-901
110
Air Cooled Refrigeration Condensing Unit
6.6.15 “
JA
” Malfunction of High Pressure Sensor
Remote
Controller
Display
JA
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Decision
Conditions
When the high pressure sensor is short circuit or open circuit.
(Not less than 4.3MPa, or 0.01MPa and below)
Supposed
Causes
Defect of high pressure sensor
Connection of low pressure sensor with wrong connection
Defect of outdoor unit PCB
Defective connection of high pressure sensor