Troubleshooting
SiENBE28-901
124
Air Cooled Refrigeration Condensing Unit
6.6.23 “
P1
” Power Supply Voltage Imbalance
Remote
Controller
Display
P1
Applicable
Models
LRMEQ5~20PY1
LRLEQ5~20PY1
Method of
Malfunction
Detection
Malfunction is detected from the voltage imbalance from the PCB.
Malfunction
Decision
Conditions
The power supply voltage causes an imbalance of not less than approx.14V?
Continue operation without deciding the malfunction.
Supposed
Causes
Open phase
Voltage imbalance between phases
Faulty main circuit capacitor
Faulty inverter PCB
Faulty K2M
Faulty main circuit wiring
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Imbalance in
supplied voltage is
in excess of 14 V
(Y1).
∗
1
YES
NO
Open phase?
YES
NO
Is the voltage
imbalance applied to
the inverter in excess
of 14 V (Y1)?
∗
2
YES
NO <When voltage monitoring is possible:>
Using a device capable of
constant recording of power
supply voltage record power
supply voltage between 3
phases (L1 ~ L2, L2 ~ L3,
L3~L1) for about one
continuous week.
No abnormalities are
observed in the power
supply, but the imbalance
in voltage recurs.
Power supply voltage imbalance
measure
Explanation for users
∗
In accordance with "notification of inspection results" accompanying spare parts.
Give the user a copy of "notification of inspection results" and leave
it up to him to improve the imbalance.
Be sure to explain to the user that
there is a "power supply imbalance"
for which DAIKIN is not responsible.
∗
1. Measure voltage at the X1M power supply
terminal block.
∗
2. Measure voltage at terminals RED, BLACK
and WHITE wires of the diode module inside
the inverter while the compressor is running.
Open phase
Normalize field cause.
Fix power supply voltage
imbalance.
Part or wiring defect
After turning the power supply
OFF, check and repair the main
circuit wiring or parts.
(1) Loose or disconnected
wiring between power
supply and inverter
(2) K2 contact disposition,
fusion or contact is poor.
(3) Loose or disconnected
noise filter
Replace the inverter PCB.