SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
127
6.6.26 “
U2
” Abnormal Power Supply Voltage
Remote
Controller
Display
U2
Applicable
Models
LRMEQ5~20PY1
LRLEQ5~20PY1
Method of
Malfunction
Detection
Malfunction is detected from the voltage of the main circuit capacitor in the inverter.
Malfunction
Decision
Conditions
When the voltage aforementioned is not less than 780V or not more than 320V, or when the
current-limiting voltage does not reach 200V or more or exceeds 740V.
Supposed
Causes
Power supply voltage drop
Instantaneous power failure
Open phase
Faulty inverter PCB
Faulty control box PCB
Faulty compressor
Faulty wiring in the main circuit
Faulty fan motor
Faulty connection of signal cable