SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
95
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
LRL(M)EQ15A, 20AY1 have 2 fans.
Cut the power supply OFF and wait for 10 minutes.
Check if any foreign
substances around
the fan.
YES
NO
Check connectors for their connections
{
For fan motor 1: Relay connectors X1A and X2A or
connectors of compressor inverter PCB
X1A and X2A
{
For fan motor 2: Relay connectors X3A and X4A or
connectors of fan inverter PCB X1A and
X2A
Check if any
connector is
disconnected.
YES
NO
Check the relay connectors for their color
{
For fan motor 1: White for all power supply and signal
cables
{
For fan motor 2: Red on the PCB side and white on the
motor side for all power supply and
signal cables
Relay connectors
have any connection
error.
YES
NO
A
Remove the foreign substances.
Insert the connector.
Correct the connection of the relay
connectors.
LRMEQ05~12AY1
LRLEQ05~12AY1
LRMEQ15, 20AY1
LRLEQ15, 20AY1
A4P
P1
N1
X5A
X3A
F1U R10
+
-
X4A
V1R
X2A
X1A
Z5C
N=1
X1A
5
X2A
5
M1F
MS
3~
RE
D
WH
T
BLK
A4P
A8P
P1
P2 N1
N2
X5A
X3A
F1U R10
+
-
X4A
V1R
X51A
X2A
X1A
Z5C
N=1
X1A
5
X2A
5
M1F
MS
3~
RED
WHT
BLK
P1
N1
X5A
X3A
F1U R10
+
-
X4A
V1R
X2A
X1A
Z9C
N=1
X3A
5
X4A
5
M2F
MS
3~
RED
WH
T
BL
K
RED
WHT
RED
RED
WHT