SiENBE28-901
Appendix (Supplementary Information)
Air Cooled Refrigeration Condensing Unit
149
7. Appendix
(Supplementary Information)
7.1
Restriction Matter of Showcase
•
The design pressure of the indoor unit must be 2.5MPa.
•
Install an R410A mechanical thermostatic expansion valve on eachlindoor unit.
•
Install an R410A solenoid valve (Max. operating differential pressure of 3.5 MPa (35 bars) or
over) on the primary side of the mechanical thermostatic expansion valve described above
for each indoor unit.
•
Install a filter on the primary side of the solenoid valve described above for each indoor unit.
Determine the filter mesh count based on the size specified by the solenoid valve and
mechanical thermostatic expansion valve being used.
•
Route the path to the indoor unit heat exchanger so that the flow or refrigerant is from top to
bottom.
•
Wlhen installing a number of indoor units, be sure to install them at the same level.
Difference in height between indoor units to be 5m or less.
•
Use either off-cycle defrosting or electric heater defrosting as the defrostingltype.
Hot-gas defrosting models cannot be used.
7.2
Selection of Expansion Valve
•
The expansion valve must use made of the Danfoss.
•
EEV (On/Off switching electric expansion valve) cannot be used.
Mechanical
thermostatic
expansion valve
Liquid solenoid
Filter
Flow of refrigerant
Evaporator outlet
Evaporator inlet
Evaporator inlet
Evaporator
inlet
Evaporator outlet
Evaporator
outlet