Troubleshooting
SiENBE28-901
100
Air Cooled Refrigeration Condensing Unit
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Connect the service checker.
Press reset and start operation
again.
Is the refrigerant
amount proper?
YES
NO
Check the
refrigerant piping
line for clogging.
YES
NO
Connect the service checker,
and the restart the system.
Check if discharge
pipe thermistor
property is normal.
(
∗
1)
YES
NO
Service Checker
Connect the service checker to compare the
temperature of discharge pipe by using service
checker with actual measurement value of discharge
pipe thermistor (Refer to
∗
1).
Check if temperature of
discharge pipe by using service
checker is the same with actual
measurement value of discharge
pipe thermistor.
YES
NO
· Discharge pipe thermistor is normal and the
temperature detection of the main PCB is also normal.
· Actually the temperature of discharge pipe is high.
Check 3
Remove the factor of overheat operation
referring to P132.
∗
1: Compare the resistance value of discharge pipe thermistor and the value based on the surface
thermometer.
(Refer to P106 for the temperature and resistance characteristics of thermistor)
Recover the refrigerant.
Conduct vacuum drying, and then
charge a proper amount of
refrigerant.
Rectify the clogging.
Replace the discharge pipe
thermistor.
Replace the main PCB (A1P).