Troubleshooting
SiENBE28-901
86
Air Cooled Refrigeration Condensing Unit
6.6.2 “
E2
” Earth Leakage
Remote
Controller
Display
E2
Applicable
Models
LRMEQ5~20AY1
LRLEQ5~20AY1
Method of
Malfunction
Detection
When there is a earth leakage (breaker ON/OFF)
Time elapsed after power-on
When there is a earth leakage (leakage detector PCB)
The continuity of the high pressure switch is checked using the protective device circuit.
Malfunction
Decision
Conditions
When there is a earth leakage (breaker ON/OFF)
Within 10 seconds after the power is turned on
When there is a earth leakage (leakage detector PCB)
If the high-pressure switch is activated but the pressure is not very high
Supposed
Causes
Compressor (or the complete product) has defective insulation.
High pressure switch connection failure
Faulty leakage detector PCB
No continuity in high pressure switch
Temporary liquid return or refrigerant slugging
Power failure during operation
Prolonged power shut down
Within 10 seconds after the power is turned on