Si12-619A
Outdoor Unit – E Series (80 / 90 / 100 Class)
Removal Procedure
341
5
Disconnect the
connectors one by one
starting from your side.
z
Connectors
S33
&
S71
:
For inverter PCB
z
Connectors
S31
&
S32
:
For SPM PCB
z
Connectors
S51
&
S101
:
For display PCB
z
Connector
S10
: For relay
PCB
z
Connectors
H1
/
H2
: For DB
(diode bridge), power wire
harnesses
AC1
(red) and
AC2
(black)
6
Remove the control
PCB.
2. Removing the
reactor
1
Remove the screw.
2
Remove the 3 screws
and lift the reactor
upward to remove it.
Step
Procedure
Points
(R6431)
(R6432)
(R6433)
(R6434)