![background image](http://html.mh-extra.com/html/daikin/3mks50dvm/3mks50dvm_service-manual_501112047.webp)
Specifications
Si12-619A
34
Specifications
60Hz 220V
Note:
1. The data are based on the conditions shown in the table below.
Model
3MKS90EVLT
4MKS100EVLT
Cooling Capacity
kW
—
—
Power Consumption
W
—
—
Running Current
A
—
—
Casing Color
Ivory White
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Model
2YC63BXD
2YC63BXD
Motor Output
W
1,920
1,920
Refrigerant Oil
Model
FVC50K
FVC50K
Charge
L
0.75
0.75
Refrigerant
Type
R-410A
R-410A
Charge
kg
3.1
3.1
Air Flow Rates
m³/min
H
54.5
54.5
M
51.2
51.2
L
46.0
46.0
cfm
H
1,924
1,924
M
1,808
1,808
L
1,624
1,624
Fan
Type
Propeller
Propeller
Motor Output
W
66
66
Running Current
A
H: 0.97 / M: 0.86 / L: 0.69
H: 0.97 / M: 0.86 / L: 0.69
Power Consumption
W
H: 86 / M: 73 / L: 55
H: 86 / M: 73 / L: 55
Starting Current
A
14.0
14.0
Dimensions (H×W×D)
mm
770×900×320
770×900×320
Packaged Dimensions (H×W×D)
mm
900×925×390
900×925×390
Weight
kg
69
69
Gross Weight
kg
78
79
Operation Sound
dBA
50
50
Piping Connection
Liquid
mm
φ
6.4×3
φ
6.4×4
Gas
mm
φ
9.5×1,
φ
12.7×1,
φ
15.9×1
φ
9.5×1,
φ
12.7×1,
φ
15.9×2
Drain
mm
φ
25.0
φ
25.0
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
No. of Wiring Connection
3 for Power Supply, 4 for Interunit Wiring
3 for Power Supply, 4 for Interunit Wiring
Max. Interunit Piping Length
m
70 (for Total of Each Room)
70 (for Total of Each Room)
m
25 (for One Room)
25 (for One Room)
Amount of Additional Charge
g/m
Chargeless
Chargeless
Max. Installation Height Difference
m
15 (between Indoor Unit and Outdoor Unit)
15 (between Indoor Unit and Outdoor Unit)
m
7.5 (between Indoor Units)
7.5 (between Indoor Units)
Drawing No.
3D052688#1
3D052684#1
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB/24°CWB
7.5m
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...