Troubleshooting
Si12-619A
218
Service Diagnosis
5.7
Shutter Drive Motor / Shutter Limit Switch Abnormality
Remote
Controller
Display
C7
Method of
Malfunction
Detection
The shutter open / close performance is detected by the limit switch attached on its structure. In
this way, the shutter drive motor and the shutter limit switch are checked for failure.
Malfunction
Decision
Conditions
When the shutter is open, the limit switch is closed.
Supposed
Causes
Shutter drive motor defective
Shutter limit switch defective
Shutter itself deformed (warped)
Shutter's sealing material too thick
Detection error by broken relay harness or disconnected connector
Detection error due to defective PCB (2)
Foreign substance in blow port
Troubleshooting
Check No.03
Refer to P.260
Turn off the power.
Check No. 03
Check the limit switch continuity.
Remove such substance.
Replace the limit switch.
Reconnect the connector or
replace the relay harness.
Replace the shutter drive
motor or the PC board (2).
Check the shutter's sealing
material.
Check the shutter for
deformation or its sealing
material.
(Q0346)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Foreign substance in
the shutter structure?
YES
NO
NO
NO
YES
Shutter closed?
NO
Shutter opening itself?
YES
YES
YES
NO
Relay harness
broken or connector
disconnected?
Limit switch on power?
Open the shutter and turn on the
power.
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...