Si12-619A
Outdoor Unit – E Series (80 / 90 / 100 Class)
Removal Procedure
335
4
Disconnect the fan
motor connector
S70
.
5
Release the fan motor
wire harness.
6
Disconnect the
motorized valve
connector
S80
.
Detach the clamp.
Just pull the push-mount
type out of position.
7
Disconnect the 4
motorized valve
connectors (for Rooms
A, B, C and D).
A : Connector
S20
(white),
B : Connector
S21
(red),
C : Connector
S22
(blue),
D : Connector
S23
(yellow).
Step
Procedure
Points
[S70]
(R6413)
(R6414)
[S80]
Clamp
(R6415)
A
B
C
D
Clamp
(R6416)