![background image](http://html.mh-extra.com/html/daikin/3mks50dvm/3mks50dvm_service-manual_501112045.webp)
Specifications
Si12-619A
32
Specifications
1.2
Outdoor Units - Cooling Only
50Hz 230-240V
Note:
1. The data are based on the conditions shown in the table below.
Model
3MKS58EVMA
3MKS75EVMA
Cooling Capacity
kW
—
—
Power Consumption
W
—
—
Running Current
A
—
—
Casing Color
Ivory White
Ivory White
Compressor
Type
Hermetically Sealed Swing Type
Hermetically Sealed Swing Type
Model
2YC36BXD
2YC45BXD
Motor Output
W
1,100
1,380
Refrigerant Oil
Model
FVC50K
FVC50K
Charge
L
0.65
0.75
Refrigerant
Type
R-410A
R-410A
Charge
kg
2.0
2.3
Air Flow Rates
m³/min
H
45
51
L
45
45
cfm
H
1,589
1,801
L
1,589
1,589
Fan
Type
Propeller
Propeller
Motor Output
W
53
53
Running Current
A
H: 0.33 / L: 0.33
H: 0.33 / L: 0.25
Power Consumption
W
H: 43 / L: 43
H: 68 / L: 46
Starting Current
A
6.8
9.2
Dimensions (H×W×D)
mm
735×936×300
735×936×300
Packaged Dimensions (H×W×D)
mm
792×992×390
792×992×390
Weight
kg
49
58
Gross Weight
kg
56
64
Operation Sound
dBA
46
48
Sound Power
dBA
59
61
Piping Connection
Liquid
mm
φ
6.4×3
φ
6.4×3
Gas
mm
φ
12.7×3
φ
12.7×2,
φ
15.9×1
Drain
mm
φ
18.0
φ
18.0
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
No. of Wiring Connection
3 for Power Supply, 4 for Interunit Wiring
3 for Power Supply, 4 for Interunit Wiring
Max. Interunit Piping Length
m
50 (for Total of Each Room)
60 (for Total of Each Room)
m
25 (for One Room)
25 (for One Room)
Amount of Additional Charge
g/m
Chargeless
Chargeless
Max. Installation Height Difference
m
15 (between Indoor Unit and Outdoor Unit)
15 (between Indoor Unit and Outdoor Unit)
m
15 (between Indoor Units)
15 (between Indoor Units)
Drawing No.
3D055029
3D055077
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Cooling
Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB
7.5m
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...