Outdoor Unit – E Series (80 / 90 / 100 Class)
Si12-619A
344
Removal Procedure
3.4
Removal of
Fan Motor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
2
Remove the 2 screws
at the bottom first.
Next, remove the 2 top
screws.
Be sure to remove the bottom
screws first. If the top screws
are removed first, the fan motor,
the center of gravity of which is
toward the front, may tilt down
or fall, getting you injured.
3
Remove the fan motor.
When reassembling, be sure to
place the wire harness lower.
(R6441)
(R6442)
2
1
(R6443)
(R6444)
Harness