Main Functions
Si12-619A
84
Function and Control
1.6
Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
The temperature difference is in the zone A.
Thermostat ON Condition
The temperature difference is above the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Wall Mounted Type
Floor standing Type
Floor/Ceiling suspended Type
Duct Connected Type
Heating
Wall Mounted Type
Floor standing Type
Floor/Ceiling suspended Type
Duct Connected Type
B
A
OFF
ON
C
Cooling : – 0.5˚C
Dry : – 0.5˚C
Room temperature - setpoint
Cooling : – 2.0˚C
Dry : – 2.5~– 2.0˚C
(R4668)
B
A
OFF
ON
C
– 1.5˚C
Room temperature - setpoint
Cooling : – 2.0˚C
Dry : – 2.5~– 2.0˚C
Cooling : – 1.0˚C
Dry : – 1.0˚C
(R6032)
B
A
OFF
ON
C
1.5˚C
Room temperature - setpoint
0˚C
(R4669)
B
A
OFF
ON
C
1.5˚C
1.0˚C
Room temperature - setpoint
0.5˚C
(R6033)
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...