![background image](http://html.mh-extra.com/html/daikin/3mks50dvm/3mks50dvm_service-manual_501112116.webp)
Si12-619A
Control Specification
Function and Control
103
3.3
Controls at Mode Changing / Start-up
3.3.1
Preheating Operation
Outline
Operate the inverter in the open phase operation with the conditions including the preheating
command from the indoor, the outdoor air temperature and discharge pipe temperature.
Detail
Preheating ON Condition
When outdoor air temperature is below 10.5°C and discharge pipe temperature is below
10.5°C, inverter in open phase operation starts. (The power consumption of compressor
during preheat operation is 35 W.)
OFF Condition
When outdoor air temperature is higher than 12°C or discharge pipe temperature is higher
than 12°C, inverter in open phase operation stops.
3.3.2
Four Way Valve Switching
Outline
Heat Pump Only
During the heating operation current must be conducted and during cooling and defrosting
current must not be conducted. In order to eliminate the switching sound (as the four way valve
coil switches from ON to OFF) when the heating is stopped, the delay switch of the four way
valve must be carried out after the operation stopped.
Detail
The OFF delay of four way valve
Energize the coil for 150 sec after unit operation is stopped.
3.3.3
Four Way Valve Operation Compensation
Outline
Heat Pump Only
At the beginning of the operation as the four way valve is switched, acquire the differential
pressure required for activating the four way valve by having output the operating frequency,
which is more than a certain fixed frequency, for a certain fixed time.
Detail
Staring Conditions
1. When starting compressor for heating.
2. When the operating mode changes from the previous time.
3. When starting compressor for rushing defrosting or resetting.
4. When starting compressor for the first time after the reset with the power is ON.
Set the lower limit frequency to 39 (model by model) Hz for 70 seconds with any conditions 1
through 4 above.
3.3.4
3-Minute Stand-by
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5
Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
FCG 3
FCG 2
FCG 1
TCG 1
TCG 2
TCG 3
2YC32
85
70
55
120
200
470
2YC36
85
70
55
150
180
300
2YC45, 2YC63
80
65
55
120
200
470
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...