Si12-619A
Outdoor Unit – E Series (50 / 52 / 58 Class)
Removal Procedure
301
1.9
Removal of the Compressor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Remove the terminal
cover
Make a note.
Be careful not to burn the
compressor terminals or the
name plate.
Warning
Since it may happen that
refrigeration oil in the
compressor will catch fire,
prepare wet cloth so as to
extinguish fire immediately.
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
will cause to arise toxic gas.)
Caution
Be careful not to get yourself
burnt with the pipes and other
parts that are heated by the
gas welding rod.
1
Remove the terminal
cover.
2
Disconnect the flag-
shaped terminals.
3
Detach the compressor
lead wire.
4
Detach the overload
protector.