Troubleshooting
Service Diagnosis
245
5.23.2 E Series (50-58 Class, 80-100 Class)
Remote
Controller
Display
L3
Outdoor Unit LED
Display
A
5
1
4
2
4
3
1
4
4
Method of
Malfunction
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
Decision
Conditions
With the compressor off, the radiation fin temperature is above 100°C.
The error is cleared when the temperature drops below 85°C (52-58 class) or 70°C (80-100
class).
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective