Troubleshooting
Si12-619A
228
Service Diagnosis
5.14
DC Fan Lock
Remote
Controller
Display
E7
Outdoor Unit LED
Display
A
5
1
4
2
4
3
4
4
4
Method of
Malfunction
Detection
A fan motor line error is detected by checking the high-voltage fan motor rpm being detected by
the Hall IC.
Malfunction
Decision
Conditions
The fan does not start in 30 seconds even when the fan motor is running.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Supposed
Causes
Fan motor breakdown
Harness or connector disconnected between fan motor and PCB or in poor contact
Foreign matters stuck in the fan
Troubleshooting
Check No.15
Refer to P.268
Turn off the power and
reconnect the connector.
Remove.
Replace the outdoor unit
fan motor.
Replace the outdoor unit
PCB.
(R2843)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Fan motor connector
disconnected?
YES
YES
NO
YES
NO
Pulse signal inputted?
NO
Foreign matters in or
around the fan?
Get started.
Check No. 15
Check the outdoor unit PCB rpm
pulse input.
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...