Si12-619A
Outdoor Unit – E Series (50 / 52 / 58 Class)
Removal Procedure
277
1.2
Removal of the Electrical Box
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Disconnect the
connecting wires
Illustrations are for 3 room
model.
1
Inside structure.
2
Disconnect the
connecting wires.
Connecting wires of the A, B,
C, D port
(1) - Black
Power supply
(2) - White
Power supply
(3) - Red
Transmission
Power Supply wires
(L) - Black
(N) - White
Fasten the wires on the
terminal board with screws.