Si12-619A
Control Specification
Function and Control
117
3.16.5
Cooling / Heating Mode Lock
Use the S15 connector to set the unit to only cool or heat.
Setting to only heat (H): Short-circuit pins 1 and 3 of the connector <S15>.
Setting to only cool (C): short-circuit pins 3 and 5 of the connector <S15>.
The following specifications apply to the connector housing and pins.
JST products Housing: VHR-5N
Pin: SVH-21T-1, 1
Note that forced operation is also possible in COOL / HEAT mode.
3.16.6
ECONO-mode-proof Setting
(E series 50-58 class, 80-100 class)
Outline
When installing in hotels, you can make ECONO mode ineffective on the outdoor unit.
Operation
The ECONO mode can be switched over between "effective" and "ineffective" by pressing the
forced operation switch (SW1) and wiring error check switch (SW3) at the same time and
holding them for 5 seconds while the compressor is stopped. The LEDs are lit in turn for 15
seconds to show the ECONO mode status.
The factory setting is "effective".
COOL mode (C)
HEAT mode (H)
5<C>3<H>1
(R1397)
effective
→
ineffective
ineffective
→
effective
LED flashing order
4
→
3
→
2
→
1
1
→
2
→
3
→
4
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...