Troubleshooting
Si12-619A
212
Service Diagnosis
5.4
Freeze-up Protection Control or High Pressure Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
High pressure control (heat pump model only)
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
The freeze-up protection control (operation halt) is activated during cooling operation
according to the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 65°C
Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...