Troubleshooting
Si12-619A
220
Service Diagnosis
Troubleshooting
Check No.10
Refer to P.266
Check the outdoor unit's LED A.
Check the indoor unit-outdoor unit
connection wires.
YES
YES
Correct the indoor unit-outdoor
unit connection wires.
Diagnose the outdoor unit.
Replace the connection wires
between the indoor and
outdoor units.
Replace indoor unit control
PCB .
Locate the cause of the
disturbance of the power supply
waveform, and correct it.
Is there any wiring error?
NO
(R6471)
Is LED A flashing?
Is the voltage 0 V?
NO
Check No. 10
Check power supply waveform.
Check the voltage of the indoor
unit-outdoor unit connection wires
between No. 1 and No. 2, and
between No 2 and No. 3.
YES
YES
NO
Is there any disturbance?
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
Rotate fan by hand.
Replace fan motor and
outdoor unit PCB .
Does fan rotate
smoothly?
NO