Si12-619A
Troubleshooting
Service Diagnosis
229
5.15
Input Over Current Detection
Remote
Controller
Display
E8
Outdoor Unit LED
Display
A
5
1
1
2
4
3
1
4
4
Method of
Malfunction
Detection
Malfunction is detected by checking the input current value.
Malfunction
Decision
Conditions
The input current is a certain value (depending on the model) or over for 2.5 seconds.
The compressor halts if the error occurs, and restarts automatically after 3 minutes stand-by.
Supposed
Causes
Over-current due to compressor failure
Over-current due to defective power transistor
Over-current due to defective inverter main circuit electrolytic capacitor
Over-current due to defective outdoor unit PCB
Error detection due to outdoor unit PCB
Over-current due to short-circuit