Si12-619A
Outdoor Unit – E Series (50 / 52 / 58 Class)
Removal Procedure
293
4
Pull up the right side
panel.
5
Loosen the 2 screws of
the wiring fixture.
2. Remove the partition plate
1
Loosen the 2 screws to
remove the partition
plate.
2
Detach the clamp of the
relay harness for the
compressor.
Step
Procedure
Points