Outdoor Unit – E Series (68 / 71 / 75 Class), D Series
Si12-619A
308
Removal Procedure
2.3
Removal of the
PCB
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1. Removing the controller
PCB
1
Remove the screw of
the PCB, and release 2
tabs.
2
Release the tabs of the
terminal board, and
open the terminal
board.
3
Disconnect each
connector on the back
of the terminal board.
4
Disconnect the
service
monitor PCB
connector.
Release the tab to remove
the service monitor PCB.