Si12-619A
Main Functions
Function and Control
91
1.12
Inverter POWERFUL Operation
Outline
In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by
increasing the indoor fan rotating speed and the compressor frequency.
Details of the
Control
When POWERFUL button is pushed in each operation mode, the fan speed / setting
temperature will be converted to the following states in a period of twenty minutes.
In case of FTK(X)S20-35D, FTK(X)S25/35E
Ex.) : POWERFUL operation in cooling mode.
Refer to “Fan Speed control” on page 81 for detail.
Operation mode
Fan speed
Target set temperature
COOL
H tap + 50 rpm
18°C
DRY
Dry rotating speed +
50 rpm
Normally targeted
temperature in dry
operation; Approx. –2°C
HEAT
H tap + 50 rpm
30°C
FAN
H tap + 50 rpm
—
AUTO
Same as cooling /
heating in POWERFUL
operation
The target is kept
unchanged
(R4560)
Target temp.
Fan
50rpm
Set temp.
18˚C
POWERFUL ON
POWERFUL OFF
H tap
Set tap
It should be the lower limit of cooling temperature.
It counts 20 min. also in the remote controller.
20min.
Ending condition: "or" in 1 to 3
1. After the lapse of 20 minutes.
2. Stop
3. POWERFUL operation is OFF.
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...