![background image](http://html.mh-extra.com/html/daikin/3mks50dvm/3mks50dvm_service-manual_501112055.webp)
Specifications
Si12-619A
42
Specifications
Duct Connected Type
50Hz 220-230-240V / 60Hz 220-230V
Note:
1. The operating sound is based on the rear side suction inlet and the external static pressure 40 Pa.
Operating sound for under side suction inlet: [operating sound for rear side suction inlet] +5 dB.
However, when installation to which the external static pressure becomes low is carried out,
5 dB or more may go up.
Model
FDXS25CVMA
FDXS35CVMA
Cooling
Heating
Cooling
Heating
Rated Capacity
2.5kW Class
3.5kW Class
Front Panel Color
—
—
Air Flow Rates
m³/min
(cfm)
H
9.5 (335)
9.5 (335)
10.0 (353)
10.0 (353)
M
8.8 (311)
8.8 (311)
9.3 (328)
9.3 (328)
L
8.0 (282)
8.0 (282)
8.5 (300)
8.5 (300)
SL
6.7 (237)
6.7 (237)
7.0 (247)
7.0 (247)
Fan
Type
Sirocco Fan
Sirocco Fan
Motor Output
W
62
62
Speed
Steps
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.49-0.47-0.45/0.49-0.47
0.49-0.47-0.45/0.49-0.47
0.49-0.47-0.45/0.49-0.47
0.49-0.47-0.45/0.49-0.47
Power Consumption (Rated)
W
100
100
100
100
Power Factor
%
92.8-92.5-92.6/92.8-92.5
92.8-92.5-92.6/92.8-92.5
92.8-92.5-92.6/92.8-92.5
92.8-92.5-92.6/92.8-92.5
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
200×900×620
200×900×620
Packaged Dimensions (H×W×D)
mm
266×1,106×751
266×1,106×751
Weight
kg
25
25
Gross Weight
kg
31
31
Operation
Sound
H/M/L/SL
dBA
35/33/31/29
35/33/31/29
35/33/31/29
35/33/31/29
External Static Pressure
Pa
40
40
Moisture Removal
L/h
1.2
—
1.9
—
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
9.5
φ
9.5
Drain
mm
VP20 (O.D
φ
26 / I.D
φ
20)
VP20 (O.D
φ
26 / I.D
φ
20)
Drawing No.
3D055393B
3D055394B
Model
FDXS50CVMA
FDXS60CVMA
Cooling
Heating
Cooling
Heating
Rated Capacity
5.0kW Class
6.0kW Class
Front Panel Color
—
—
Air Flow Rates
m³/min
(cfm)
H
12.0 (424)
12.0 (424)
16.0 (565)
16.0 (565)
M
11.0 (388)
11.0 (388)
14.8 (523)
14.8 (523)
L
10.0 (353)
10.0 (353)
13.5 (477)
13.5 (477)
SL
8.4 (297)
8.4 (297)
11.2 (395)
11.2 (395)
Fan
Type
Sirocco Fan
Sirocco Fan
Motor Output
W
130
130
Speed
Steps
5 Steps, Quiet, Auto
5 Steps, Quiet, Auto
Air Filter
Removable-Washable-Mildew Proof
Removable-Washable-Mildew Proof
Running Current (Rated)
A
0.69-0.66-0.63/0.69-0.66
0.69-0.66-0.63/0.69-0.66
0.80-0.77-0.74/0.80-0.77
0.78-0.75-0.72/0.78-0.75
Power Consumption (Rated)
W
140
140
160
160
Power Factor
%
92.2-92.2-92.6/92.2-92.2
92.2-92.2-92.6/92.2-92.2
90.9-90.3-90.1/90.9-90.3
93.2-92.8-92.6/93.2-92.8
Temperature Control
Microcomputer Control
Microcomputer Control
Dimensions (H×W×D)
mm
200×900×620
200×1,100×620
Packaged Dimensions (H×W×D)
mm
266×1,106×751
266×1,306×751
Weight
kg
27
30
Gross Weight
kg
34
37
Operation
Sound
H/M/L/SL
dBA
37/35/33/31
37/35/33/31
38/36/34/32
38/36/34/32
Sound Power
H
dBA
55
55
56
56
External Static Pressure
Pa
40
40
Moisture Removal
L/h
—
—
Heat Insulation
Both Liquid and Gas Pipes
Both Liquid and Gas Pipes
Piping Connection
Liquid
mm
φ
6.4
φ
6.4
Gas
mm
φ
12.7
φ
12.7
Drain
mm
VP20 (O.D
φ
26 / I.D
φ
20)
VP20 (O.D
φ
26 / I.D
φ
20)
Drawing No.
3D054916A
3D054917A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Summary of Contents for 3MKS50DVM
Page 13: ...Introduction Si12 619A xii ...
Page 131: ...Control Specification Si12 619A 118 Function and Control ...
Page 213: ...Instruction Si12 619A 200 Operation Manual ...
Page 283: ...Check Si12 619A 270 Service Diagnosis ...
Page 302: ...Si12 619A Outdoor Unit E Series 50 52 58 Class Removal Procedure 289 Step Procedure Points ...
Page 385: ...Wiring Diagrams Si12 619A 372 Appendix FTK X S50 60 71FVLT ...
Page 399: ...Si12 619A vi Index ...