Outdoor Unit – E Series (80 / 90 / 100 Class)
Si12-619A
354
Removal Procedure
3.7
Removal of
Compressor
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
1
Remove the terminal
cover.
2
Pull out the 3 leads
using long-nose pliers.
U:red, V:yellow, W:blue
3
Remove the OL.
4
Remove the 3 screws.
(R6466)
(R6467)
W(blue)
U(red)
V(yellow)
OL
(R6468)