Outdoor Unit – E Series (80 / 90 / 100 Class)
Si12-619A
352
Removal Procedure
4
Remove the sound
blanket (outer sleeve).
The sound blanket is fragile.
Be careful of the notches of
the compressor mount (3
locations).
5
Remove the sound
blanket (top lower).
The sound blanket is fragile.
Carefully pass the discharge
pipe through it.
6
Open the sound blanket
(inner sleeve) and
remove part of the
muffler.
The sound blanket is fragile.
Be careful of the notches of
the compressor mount (3
locations).
Step
Procedure
Points
(R6462)
(R6463)
(R6464)