7.1.2 Settings
Select
8. Start / Stop Temperature
1. Heaters
• Set the following parameters.
Refer to the previous section to get further informa-
tion on these parameters.
Heaters’ Start / Stop Temperatures:
Set the start and stop temperature of
each heating output. The stop tem-
perature must be at least 0.5°F (0.3°C)
greater than the start temperature for
a given heater.
Hi Fires’ Start / Stop Temperatures:
Set the start and stop temperatures of
each hi fire heating output. The stop temperature must be at least 0.5°F
(0.3°C) greater than the start temperature for a given heater.
Only available if the hi fire option is enabled (s.4.5).
Empty Zone Heaters’ Start/Stop Temperatures:
Only shown for heaters that operate in empty zones (s. 4.9).
Set the start and stop temperatures of empty zone heaters. The stop temperature
must be at least 0.5°F (0.3°C) greater than the start temperature for a given
heater.
Main Menu
7.
Light Settings
8.
Start / Stop Temperature
Start / Stop Temperature Settings
1.
Heaters
2.
Fan Stages
3.
Coolings
4.
Tunnel Curtain 1
5.
Tunnel Curtain 2
6.
Clock Outputs
7.
0-10V Output 1
8.
0-10V Output 2
9.
0-10V Output 3
10.
0-10V Output 4
11.
Alarms
Exit: Press Back
Submenu: Press Enter
Press to Select an Item
Heater Start / Stop Temperature
Heater 1
Start Temperature
68.0 °F
Stop Temperature
69.0 °F
Heater 1 Hi Fire
Start Temperature
67.0 °F
Stop Temperature
69.0 °F
(...)
Heater 8
Empty Zone
Start Temperature
32.0 °F
Stop Temperature
33.0 °F
Exit: Press Back
Change: Press Modify
Press to Select an Item