75
EXPERT 64EU rev.03
EXPERT 64EU
Cycle Time :
Time that is required to perform a
whole RH compensation heating
cycle. Adjustable from 15 to 900 sec-
onds. It must be set to a greater value
than the On time.
Mist Shutoff:
The following parameter is only accessible if Mist Shutoff
function has been activated in the installation setup (s.
4.4). Refer to s. 10.1.3 for further information on this
function.
• Set the humidity level above which
the cooling outputs stop operating.
Adjustable from 20 to 100% of
humidity. Select “
Off
” to deactivate
this function.
Mist on Lo % Relative Humidity:
The following parameters are only accessible if RH compensation function
“
Mist on Low R. Humidity
” has been activated in the installation setup (s.
4.4). Refer to s. 10.1.3 for further information on this function.
• Lo Set Point :
Humidity level below which the mist cooling
outputs start operating according to a timer.
Adjustable from 20 to 100% of humidity or
select “
Off
” to deactivate this function.
• On/Off Times:
Mist cooling outputs’ timer that is activated when the humidity level is too low.
The On and Off times are adjustable from 0 to 15 minutes.
GRAPHIC:
Mist cooling outputs’ timer
ON
ON TIME
OFF
OFF
TIME
Main Menu
9.
Advanced Settings
10.
Select Program
Advanced Settings
10.
Alarms
11.
Relative Humidity Compensation
RH Compensation Settings
Relative Humidity Compensation
Add Min Vent sec
60 sec
RH Setpoint
65 %
Heater Compensation
Minimum On Time
15 sec
Maximum On Time
45 sec
Cycle Time
300 sec
Mist Shutoff
85 %
Mist On Low % Relative Humidity
Low Setpoint
30 %
On Time
0:30 (m:s)
Off Time
2:00 (m:s)
Exit: Press Back
Change: Press Modify
Press to Select an Item