63
EXPERT 64EU rev.03
EXPERT 64EU
6.5
Cooling Outputs
6.5.1 Principle of Operation
The controller has three cooling outputs that can be used to operate cooling devices
such as mist units. The intensity of these outputs increases gradually as the room
temperature increases. The following diagram illustrates the cooling outputs’ opera-
tion.
The cooling outputs start operating according to a timer (On Time 1 & Off time 1)
when their start temperature is reached. The outputs’ timer gradually changes as the
temperature increases. It reaches its second settings (On Time 2 & Off time 2) when
the room temperature reaches the
Maximum Temperature.
The cooling outputs’ start and stop temperatures are related to the main set point.
This means that when the set point changes, they are consequently adjusted.
The activation of the cooling outputs can be confined to a user-defined time range.
This allows to deactivate it during night for instance.
GRAPHIC :
Cooling outputs’ Operation
Room
Temperature
COOLING
OUTPUTS’
TIMER
On Time 2
or Off Time 2
On Time 1
or Off Time 1
Off
Start T°
Max T
°
Stop T°
Set Point
THE COOLING
OUTPUT IS ATIVATED
USING ON TIME 1
AND OFF TIME 1
COOLING
OUTPUT IS
INACTIVE
THE COOLING
OUTPUT USES
ON TIME 2
AND OFF TIME 2