61
EXPERT 64EU rev.03
EXPERT 64EU
6.4.2.3
Inlet Settings: Openings
The following procedure shows how to program the inlet openings (for inlets that are
controlled by an IM-010 module only). If the air inlets are controlled by a Potentiometer
Feedback Inlet Controller (Pot.Ctrl), set the openings directly on the external controller.
Refer to section 4.5 to select which type of module is used for the inlet control (IM-010
or pot.ctrl).
Select
6. Inlet Setup
2. Opening *
* Only accessible for inlets controlled by
IC-010 modules.
• Set the following parameters.
(Refer to the previous section to get further informa-
tion on these parameters)
Display:
The following parameters concern the
selected air inlet.
Opening Stage 0:
Set the opening of the selected inlet
when the fans are turned off during
the minimum ventilation cycles.
Opening Stages 1-15:
Set the opening that is associated with the activation of each fan stage.
Adjustable from 0 to 100%.
Opening Stages 1-14 Max:
Set the opening that is attained when a variable fan stage reaches its full
speed. Adjustable from 0 to 100%.
Max Opening:
Maximum opening of the air inlet that is reached beyond the last fan stage.
Adjustable from 0 to 100%.
Degrees to Max Opening:
Number of degrees required to reach the inlet’s maximum opening, from the
last reference point. Adjustable from 0.5 to 20.0°F (0.3 to 11.1°C).
Max Opening Mode:
Select the proper way for the inlet to reach its maximum opening stage.
Progressive / Dump (s. 6.4.1.2).
Main Menu
1.
Current condition
2.
History
3.
Animal Age & Mortality
4.
Set Point
5.
Minimum Ventilation
6.
Inlet Setup
7.
Light Settings
8.
Start / Stop Temperature
9.
Advanced Settings
10.
Select Program
11.
Alarm Log
12.
Controller Setup
Submenu: Press Enter
Press
to Select an Item
Inlet Setup
1.
Probe Assignment
2.
Opening
3.
Temperature Compensation
Exit: Press Back Submenu: Press Enter
Press
to Select an Item
Inlet Opening
Display
Inlet X
Opening Stage 0
0 %
Opening Stage 1
5 %
Opening Stage 1 Max
10 %
Opening Stage 2
10 %
Opening Stage 2 Max
20 %
(...)
Opening Stage 15 Max
80 %
Maximum Opening
100 %
Degrees to Max Opening
5.0°F
Max Opening Mode Progres./Dumping
Exit: Press Back
Change: Press Modify
Press To Select an Item