58
EXPERT 64EU rev.03
EXPERT 64EU
6.4.1.2
Inlets’ Specific Functions
The following functions do not apply to chimney dampers.
TEMPERATURE COMPENSATION ON THE INLETS’ OPENING
A compensation can be activated to ensure a certain uniformity in the room tempera-
ture: the air inlet positions are automatically adjusted when the inlet temperature
probes’ reading differs from the average temperature read by the controller.
The inlet temperature compensation is expressed as a percentage per degree differ-
ence between the average controller temperature and the average reading of the
probes assigned to the inlet. It determines by how much the inlet must open or close
to help reduce the temperature differences in the building. For each degree above or
below the average temperature, the inlet will open or close using the compensation
value assigned by the user. For example, if the compensation value is set to 2%/°F
and the inlet's probes read 3°F above the average controller temperature, the inlet
will open 6% to help decrease the temperature in that zone.
STATIC PRESSURE COMPENSATION ON THE INLETS’ OPENING
The static pressure compensation is expressed as a percentage per 0.01 inch of water
(%/0.01"WC). It determines by how much the inlet must open or close to help reduce
or enhance the static pressure in the building according to the set points. For each
0.01 "WC above the high static pressure set point or below the low static pressure set
point, the inlet will open or close using the compensation value assigned by the user.
For example, if the compensation value is set to 1%/0.01"WC and the static pressure
is 0.05 "WC above the high static pressure set point, the inlet will open of 5% to help
decrease the static pressure in the building.