56
EXPERT 64EU rev.03
EXPERT 64EU
Minimum Outside Temperature:
Outside temperature below which the tunnel curtain remains closed. Adjustable
from 0.1 to 100 °F (-17.7 to 37.8 °C). Select “Off” to deactivate this function.
Only available if an outside temperature probe is used (s. 4.4)
Curtain’s opening times:
(if the curtain is based on the temperature only)
Select the opening time that is associated with the activation of each fan
stage. Adjustable from 0 to 15 minutes.
Low/High Pressure Limits:
(if the curtain is based on the static pressure only)
Set the static pressure level below/above which the curtain can start to close/
open according to a timer.
Seasonal Low/High Pressure Limits:
(if the curtain is based on the static pres-
sure only)
Set the static pressure level below/above which the curtain can start to close/
open according to a timer. Set the high and low limits separately for both the
winter and summer seasons.
Only shown if the outside temperature probe is activated (s. 4.4).
Pre-opening Delay:
(if the curtain is based on the static pressure only)
Opening time of the curtain before the start-up of tunnel fans. Adjustable from
0 to 30 sec.
Open / Close / Off Times:
(if the curtain is based on the static pressure only)
Set the curtain’s opening and closing time delays to the desired value. This
timer is used when the static pressure level exceeds the high or low pressure
limits. Adjustable from 0 to 30 minutes.