28
EXPERT 64EU rev.03
EXPERT 64EU
4.7 Assignment of Variable Outputs
4.7.1 Principle of Operation
Up to two variable outputs can be used to provide variable ventilation. The assign-
ment allows to determine how and when these outputs are activated within the
ventilation stages. The variable outputs’ status must be specified for each activated
fan stage:
Var.
: the variable output is activated at its minimum intensity when its associated
fan stage starts. The variable fans increase in speed as the fan stage progresses.
ON
: the variable output acts as an ON/OFF output. It is activated at its full capac-
ity when its associated fan stage starts.
OFF
: the variable output is not activated.
(Refer to section 6.2.1.2 for further information on the variable outputs.)
THE LAST FAN STAGE MUST NOT BE CONFIGURED IN VARIABLE MODE.
IF THE LAST FAN STAGE USES A VARIABLE OUTPUT, IT MUST BE SET
AS AN ON/OFF OUTPUT.
4.7.2 Making the Assignment
Select
12. Controller Setup
6. Variable Output Assignment*
* Only accessible from the installer mode (s. 4.2)
and if variable outputs are enabled (s. 4.5).
• Set the status of both variable out-
puts for each activated fan stage. Se-
lect
“Var.”
for the variable output to
act as a variable output. Select
“On”
for the output to act as an On/Off out-
put or
“Off”
to disable the selected
output within the selected fan stage.
:$51,1*
Main Menu
11.
Alarm Log
12.
Controller Setup
Controller Setup
6.
Variable Output Assignment
7.
Probe Assignment
8.
Version
9.
Test Mode
Submenu: Press Enter
Press
to Select an Item
Variable Output Assignment
Fan Stage 1 Variable 1
Var
Variable 2
Var
Fan Stage 2 Variable 1
Var
Variable 2
Var
Fan Stage 3 Variable 1
On
Variable 2
On
Fan Stage 4 Variable 1
Off
Variable 2
Off
(...)
Fan Stage 15 Variable 1
Off
Exit: Press BackChange: Press Modify
Press to Select an Item