42
EXPERT 64EU rev.03
EXPERT 64EU
6.1.5.3
Minimum Ventilation Relay Selection
I. If the relay selection does not change over time:
The following procedure shows how to select the fan relays that are used to ensure
the minimum ventilation cycles in the case where the relay selection does not change
over time. If the relay selection changes over time, the relay selection shown in this
menu then refers to the current relays in use, as defined by the animal age.
Select
5. Minimum Ventilation
2. Current Fan Relay Assignment
This menu allows to select fan relays
that are used during the minimum ven-
tilation cycles, in the case where the
relay selection does not change over
time (“
Change Fan Relays with Age”
function disabled in section 6.1.5.1).
• Select the fan relays as follows:
-
If the fan selection alternates during the minimum ventilation cycles:
Select the bank of all fan relays that will alternate successively during the
minimum ventilation cycles;
-
If the fan selection does not alternate during the minimum ventilation cycles:
Select the fan relays that are simultaneously enabled during the cycles.
Main Menu
5.
Minimum Ventilation
6.
Inlet Setup
7.
Light Settings
8.
Start / Stop Temperature
9.
Advanced Settings
10.
Select Program
11.
Alarm Log
12.
Controller Setup
Submenu: Press Enter
Press
to Select an Item
Minimum Ventilation
2.
Current Fan Relay Assignment
3.
Curve Settings (10 Steps)
4.
Fan Relay Assignment
5.
Options
Min. Vent. Current Fan Relays
1
2 3 4 5 6 7 8
--- --- --- --- --- --- --- ---
9
10
11
12
13
14
15
16
--- --- --- --- --- --- --- ---
17
18
19
20
21
22
23
24
--- --- --- --- --- --- --- ---
25
26
27
28
29
30
31
32
--- --- --- --- --- --- --- ---
Exit: Press Back
Change: Press Modify
Press
to Select an Item