EXPERT 64EU rev.03
EXPERT 64EU
6.4
Inlets & Chimney Dampers
6.4.1 Principle of Operation
6.4.1.1
Inlets and Chimney Dampers’ Operation
The opening/closing of chimney dampers and air inlets is linked with the activation of
the fan stages. The user sets an inlet and a damper opening associated with each fan
stage. When the start temperature of a fan stage is reached, the inlets and damper
reach the opening associated with that stage.
During the minimum ventilation cycles:
When the fans are off: the inlets/dampers are at the opening defined for stage 0.
When the fans are on: the inlet/damper are at the opening defined for stage 1.
With Variable Outputs:
If variable stages are used, two additional openings must be set: an opening corre-
sponding to the beginning of the variable fan stage and an opening that is reached
when the variable fan stage attains its maximum speed.
GRAPHIC :
Inlet/Chimney Dampers’ Operation
STAGE 0
ROOM T°
SET POINT
STAGE 2
STAGE 2 MAX
STAGE 3
STAGE 1
STAGE 1 MAX
STAGE 1
BANDWIDTH
STAGE 2
START T°
INLET /
CHIMNEY DAMPER
OPENING(%)
STAGE 2
BANDWIDTH
STAGE 3
STOP T°
STAGE 3
START T°
MINIMUM
VENTILATION