EXTENDING A PROBE:
Each probe can be extended up to 500 feet (150 meters).
To extend a probe:
Use a shielded cable of outside diameter between 0.245 and 0.260 in (6.22 and 6.60
mm) (the cable dimensions should not be under 18 AWG) to ensure the cable entry is
liquid tight.
Do not ground the shielding.
It is preferable to solder the cable joint to ensure a proper contact between the two
cables.
Do not run probe cables next to other power cables.
When crossing over other cables, cross at 90°.
DEFECTIVE TEMPERATURE PROBES:
An alarm is generated when a defective probe is detected. The defective temperature
probes are identified in the
"11. Alarm Log"
menu. Refer to chapter 11 for further
information on the alarms.
2.2.3 Alarm Connection
There are two types of alarms on the market. One type activates when
current is cut off at its input, whereas the other activates when current
is supplied at its input. For an alarm of the first type, use the NC
terminal as shown on the wiring diagram. For an alarm of the second
type, use the NO terminal.
2.2.4 0-10V Output Connection
It is recommended to use a 18 to 22 AWG wire to connect the devices to the 0-10V
outputs. This type of output can be used to connect various devices such as heaters,
lights, fans, chimney dampers, etc.