41
EXPERT 64EU rev.03
EXPERT 64EU
6.1.5.2
Minimum Ventilation Timer Settings
The timer’s parameters cannot be modified if they are automatically defined by a curve.
If the curve is enabled, the following menu displays the value of the parameters as
calculated by the curve. Refer to section 6.1.5.4 to set up the curve parameters.
Select
5. Minimum Ventilation
1. Current Settings
• Set the following parameters:
(Refer to the previous sections to get further informa-
tion on these parameters)
Number of Fans per Group:
Select the number of fan relays that are
simultaneously running within a fan group.
Only accessible if the “Alternate Fan during On Time”
option is enabled in the previous section.
Number of Groups per On Time:
Select the number of fan groups that
are successively enabled during one
On Time of the minimum ventilation
cycles.
Fan Group Run Time:
Select the running time used by all fan groups.
Only accessible if the “Alternate Fan during On Time” option is enabled in the previous section.
Total On Time:
- If fans alternate during the minimum ventilation cycles:
This value represents the On Time of a minimum ventilation cycle: it is
automatically defined by the number of fan groups multiplied by the run-
ning time of a group; therefore, it cannot be modified.
- If fans do not alternate during the minimum ventilation cycles:
This value represents the On Time of a minimum ventilation cycle. Set it to
the desired value.
Off Time:
Set the minimum ventilation timer’s Off Time to the desired value.
Variable 1-2 Speed:
Set the speed of each variable output used in the minimum ventilation cycles.
Select “Off” to disable a variable output in minimum ventilation.
Main Menu
5.
Minimum Ventilation
6.
Inlet Setup
7.
Light Settings
8.
Start / Stop Temperature
9.
Advanced Settings
10.
Select Program
11.
Alarm Log
12.
Controller Setup
Submenu: Press Enter
Press
to Select an Item
Minimum Ventilation
1.
Current Settings
2.
Current Fan Relay Assignment
Min. Vent. Current Settings
Current Curve Status :
Off
Current Animal Age :
Off days
Nbr.Fans per Group :
6 fans
Nbr.Groups per OnTime :
10 group
Fan Group Run Time :
2:00 (m:s)
Total On Time :
2:00 (m:s)
Off Time :
3:00 (m:s)
Variable 1 Speed :
50 %
Variable 2 Speed :
50 %
Exit: Press Back
Change: Press Modify
Press to Select an Item