Node
DRVPW+L
DR_GND
DRVPW-L
Drive
Power
supply
Drive
Power
supply
[See Note 4]
[See Note 3]
[See Note 4]
*
24
controller out
[-1…+1]
OPA548
-
1
OPA548
DRVPW+L
DRVPW+L
DRVPW-L
DRVPW-L
M+
M
-
unbalanced
connection
balanced
connection
DR_GND
Fig. 10-16:
Motor connection circuit NY4130
Notes
1. Follow this cabling instruction:
Shielded cable is recommended, but not mandatory.
If shielded cable is used, the shielding on the NYCe 4000 side of the
cable must be connected to Shield (house connector).
Connect the other side to a convenient metal part or leave it open.
2. Connect the DR_GND of the drive power to the housing and/or safety
earth (if this is not already the case).
3. Connect the NYCe 4000, a power supply or other equipment on a metal
frame or mounting base and make sure there is a galvanic contact.
4. A fuse must be installed between the +V of the drive power supply and
DRVPW+L on the node, and between the -V of the drive power supply
and DRVPW-L on the node. The fuses are mandatory by safety
regulations and must be UL recognized. See NYCe 4000 Standard
Housings and Accessories manual for detailed information about fuses.
M0
M1
DC motor balanced
DC motor unbalanced
M1+
M2+
+V
+V
M1–
M2–
–V
NYCe 4000 Multi-axis motion control system Hardware Sys‐
tem Manual
121/233
NY4130: DC Drive Module
R911337671_Edition 18 Bosch Rexroth AG