Fig. 7-7:
Location of the "recovery mode" jumper
3.
Install the MCU in the node and power-up the MCU.
3.1
Position the MCU in the front slot guides and gently slide the
module into the slot. Align the connectors of the module with the
connectors on the system backplane. Push the module into the
backplane connectors.
Do not use excessive force to prevent damage to the connector
pins of the module or the backplane connectors.
3.2
Tighten the two screws on the cover plate of the NY4114
module.
3.3
Connect the network connection(s) to the NY4114 module.
3.4
Switch on the 24V System power supply.
3.5
Wait until the "MCU" LED on the NY4114 is fast flashing green/
orange.
4.
Connect to the web server of the MCU.
Enter in the address field of the web browser on the PC the default IP
address 192.168.41.14. The "Recovery Bootloader" page appears.